The MVE soft starter is a powerful and reliable solution for your medium voltage starting requirements. An easy-to-use graphical interface and comprehensive built-in motor/load protection make this a well balanced solution for your medium voltage needs. MVE brings together sophisticated soft start motor control functionality in a robust yet compact physical configuration. Medium voltage installations are complex enough without making the starter hard to use as well. MVE is packed with features designed to make your life easier, including real language feedback messages, so you don't have to look up codes to know what's happening. Built-in monitoring and indicators, and extensive on-board input and output functionality reduce the needs for space and cost of auxiliary equipment, while simplifying installation. Real-time graphs of motor operating performance and current quickly and clearly illustrate exactly how your motor is performing. No fuss, no trouble - a smoother start in every sense. We don't just get you started, we're committed to keeping you running smoothly too. Our dedicated diagnostic tools simplify support and maintenance. The MV Diagnostic Board is a data acquisition and recording board that is provided as standard with all AuCom MV products. The MV Diagnostic Board records waveforms that can help diagnose problems with the starter’s installation or operation, including: The 99-place event log records time-stamped details of operation and performance, making it easier than ever to track how your motor is performing. An eight position trip log records trip states and operating conditions at the time of trip, including: AuCom Interface Board Technology (IBT), a unique concept within the medium voltage soft starter market, separates the core starter control system (including the starter’s controller and complex, time critical algorithmic processing) from the medium voltage power section. Fibre optic wires connect the control and power sections of the starter through the interface board, eliminating the need for any copper wiring and providing complete galvanic isolation of the low voltage compartment. We can retrofit MVE into your existing system. Turn-key MVE kit type soft starters can be installed with minimal downtime. Update your old equipment with a cost-effective, reliable retrofit solution. IP00 kits are available for qualified integrators to incorporate into their enclosures and switchgear. IP00 kits include the SCR power section, controller module, fiber-optic cables and 24VAC/VDC power supply.A medium voltage solution you can trust
Take Control from the Start
Knowledge is Power
Diagnostics
Detailed Event Log
Even safer with IBT technology
Retrofit solutions
IP00 kits for integrators
MVE IP00 Soft Starter
The MVE soft starter is a powerful and reliable solution for your medium voltage starting requirements. An easy-to-use graphical interface and comprehensive built-in motor/load protection make this a well balanced solution for your medium voltage needs. MVE brings together sophisticated soft start motor control functionality in a robust yet compact physical configuration.

Features
Motor Control
ramp startProtection
Accessories
Communication Options
General
Current Range
70 - 1700 A
Supply
Mains Voltage
MVE-xxxx-V02
2.3 kV Phase-phase
MVE-xxxx-V04
4.2 kV Phase-phase
MVE-xxxx-V06
6.6 kV Phase-phase
MVE-xxxx-V11
10/11 kV Phase-phase
MVE-xxxx-V13
13.2-13.8 kV Phase-phase
Control voltage
85 ~ 264 VAC or 90 ~ 350 VDC*
Rated Frequency
50/60 Hz
Rated lightning impulse withstand voltage (Up)
2.3 - 6.6 kV
60 kV
10/11 kV
75 kV
13.2/13.8 kV
95 KV
Rated short-time withstand current
(symmetrical RMS) (lk)
50 kA**
Inputs on Controller
Start (C23, C24)
24 VDC, 8 mA approx
Stop (C31, C32)
24 VDC, 8 mA approx
Reset (C41, C42)
24 VDC, 8 mA approx
Input A (C53, C54)
24 VDC, 8 mA approx
Input B (C63, C64)
24 VDC, 8 mA approx
Motor thermistor (B4, B5)
Trip point > 2.4 kΩ
NOTE: All control inputs are potential free. Do not apply external voltage to these inputs.
Outputs
Ratings of output relays on Controller
10 A @ 250 VAC resistive
6 A @ 250 VAC 15 p.f. 0.3
10 A @ 30 VDC resistive
Outputs
Output Relay A (43, 44)
Normally Open
Output Relay B (51, 52, 54)
Changeover
Output Relay C (61, 62, 64)
Changeover
Analog output (B10, B11)
0-20 mA or 4-20 mA
Environmental
Ratings of output relays on Controller
10 A @ 250 VAC resistive
6 A @ 250 VAC 15 p.f. 0.3
10 A @ 30 VDC resistive
Outputs
Output Relay A (43, 44)
Normally Open
Output Relay B (51, 52, 54)
Changeover
Output Relay C (61, 62, 64)
Changeover
Analog output (B10, B11)
0-20 mA or 4-20 mA
Environmental
Degree of Protection
Power Assembly
IP00
Controller
IP54 / NEM12
Operating Temperature
-10 °C to +60 °C, above 50 °C with derating
Humidity
5% to 95% Relative Humidity
Storage Temperature
-25 °C to +70 °C
Humidity
5% to 95% Relative Humidity
Operating Altitude
1000 m ASL, higher with derating
Polution Degree
Pollution Degree 3
Vibration
Designed to IEC 60068
Equipment Class (EMC)
Class A
EMC Emission
IEC 60947-4-2