The CSX is a compact and lightweight unit, so it is suitable for installation in small spaces and is the ideal replacement for older starters. The CSX is easy to configure, with three simple adjustments. Select the initial start voltage, start ramp time and stop ramp time (if required), and the starter is ready to go. Rotary dials allow reliable, repeatable confguration with no need to navigate through a menu and no difficult-to-use dip switches. Integrated bypass contactors simplify installation by reducing the need to select and connect additional equipment. Because the contactors are already contained within the starter, the overall size of the installation is also smaller. Bypassing the starter while the motor is running reduces the amount of heating, so the starter can usually be installed with no additional ventilation. CSXi soft starters integrate into your existing DeviceNet, Modbus, Profibus or Ethernet network using easy-to-install plug-in communication interfaces. The optional remote operator can be installed to provide remote feedback, including current, temperature and starter status.Features
Compact size
Easy-to-use adjustments
Integrated bypass contactors
Accessories
Communications
CSX Compact Low Voltage Soft Starter
CSX soft start controllers are a reliable, easy to use soft start solution for your motor. Designed for maximum simplicity, these compact starters provide timed voltage ramp soft start and soft stop, and are perfect for fitting into your existing motor control centre. The CSX's small size and integrated bypass relays make installation easy, and allow the soft starter to fit in compact enclosures with limited ventilation. Configuration is as simple as three rotary switches, and remote display and communication options allow trouble-free integration into common control networks.

Low Voltage Soft Starter
Mains Supply
Mains voltage (L1, L2, L3)
CSX-xxx-V4
3 x 200 VAC ~ 440 VAC (+ 10% / - 15%)
CSX-xxx-V6
3 x 200 VAC ~ 575 VAC (+ 10% / - 15%)
Mains frequency (at start)
45 Hz to 66 Hz
Rated insulation voltage
600 VAC
Form designation
Bypassed semiconductor motor starter form 1
Control Voltage (A1, A2, A3)
CSX-xxx-xx-C1
110-240 VAC (+ 10% / - 15%)
or 380-440 VAC (+ 10% / - 15%)
CSX-xxx-xx-C2
24 VAC/VDC (± 20%)
Current consumption (during run)
< 100 mA
Current consumption (at power-up)
CSX-xxx-xx-C1
10 A
CSX-xxx-xx-C2
2 A
Inputs
Start (terminal 01)
Normally Open, 300 VAC max
Stop (terminal 02)
Normally Closed, 300 VAC max
Outputs
Main contactor (terminals 13, 14)
Normally Open
6 A, 30 VDC resistive / 2 A, 400 VAC, AC11
Environmental
Degree of protection CSX-007 to CSX-055
IP20
Degree of protection CSX-075 to CSX-110
IP00
Operating temperatures
- 10 °C to + 60 °C
Humidity
5% to 95% Relative Humidity
Pollution degree
Pollution Degree 3
Vibration
IEC 60068 Test Fc Sinusoidal
4 Hz to 13.2 Hz: ± 1 mm displacement
13.2 Hz to 200 Hz: ± 0.7 g
EMC Emission
Equipment class (EMC)
Class A
Conducted radio frequency emission
0.15 MHz to 0.5 MHz: < 90 dB (µV)
0.5 MHz to 5 MHz: < 76 dB (µV)
5 MHz to 30 MHz: 80-60 dB (µV)
Radiated radio frequency emission
30 MHz to 230 MHz: < 30 dB (µV/m)
230 MHz to 1000 MHz: < 37 dB (µV/m)
This product has been designed as Class A equipment. Use of this product in domestic environments may cause radio interference, in which case the user may be required to employ additional mitigation methods.
EMC Immunity
Electrostatic discharge
4 kV contact discharge, 8 kV air discharge
Radio frequency electromagnetic field
0.15 MHz to 1000 MHz: 140 dB (µV)
Rated impulse withstand voltage (Fast transients 5/50 ns)
2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption
100 ms (at 40% nominal voltage)
Harmonics and distortion
IEC61000-2-4 (Class 3), EN/IEC61800-3
Short Circuit
Rated short-circuit current CSX-007 to CSX-037
5 kA
Rated short-circuit current CSX-045 to CSX-110
10 kA
Heat Dissipation
During Start
3 watts / ampere
During Run
10 watts typical
Approvals
C-tick
IEC 60947
UL / C-UL
UL 508
CE
IEC 60947
CCC
GB 14048.6
Lloyds
IEC 60947